Dialog "Device Messages" > "Hardware" Tab - Siemens Sirius 3RK3 System Manual

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Release
Status
Release denied, already
released
Release denied due to incorrect
configuration CRC
Release canceled
Release canceled due to
incorrect configuration release
CRC
8.4.1.4
Dialog "Device messages" > "Hardware" tab
The configuration supports the following messages:
General
Status
Reset implemented
Reset not possible
Overview of bus interfaces
Status
DP bus error
SC bus error
Device self-test
Status
Self-test active
Self-test ok.
Self-test error
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
Symbol
Meaning
yellow
The user is trying to release an already released configuration by means of
the configuration release command.
red
The user tried to release a configuration whose configuration CRC does not
match the configuration CRC to be released.
CRC: Cyclic Redundancy Check which saves all safety-relevant
configuration data.
yellow
An already released configuration was canceled by means of the
configuration release command.
red
The configuration release CRC in the release data has a value other than
"0" and deviates from the value calculated by the safety relay.
Symbol
Meaning
green
All error sources were eliminated and could be acknowledged.
yellow
At least one error cannot be acknowledged since the error cause still exists.
Symbol
Meaning
red
Communication via the fieldbus interface PROFIBUS DP is interrupted.
red
Communication via the device bus interface is interrupted.
Symbol
Meaning
blue
Device self-test running.
green
The device self-test was finished without an error.
red
The device self-test detected an error
Diagnostics / service
8.4 Diagnostics with MSS ES
259