Creating The Safety Program - Siemens Sirius 3RK3 System Manual

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Getting Started

4.7 Creating the safety program

4.7
Creating the safety program
Configuration
Step
Activity
Drag the "ESPE" element from the
1
"Monitoring functions" folder to the work
space.
Open the "Properties - ESPE" dialog box
2
by double-clicking the block.
Select the following in the "Parameter >
Input" directory:
The "Type" parameter, and define this
as "2-channel (NCNC)".
The "IN1" parameter, and connect this
to "SLOT3_F-IN1".
The "IN2" parameter is automatically
set to "SLOT3_F-IN2".
Close the window by clicking "OK".
Drag the "EMERGENCY STOP" element
3
from the "Monitoring functions" folder to the
work space.
Open the "Properties - EMERGENCY
STOP" dialog box by double-clicking the
block.
Select the following in the "Parameter >
Input" directory:
The "Type" parameter, and define this
as "2-channel (NCNC)".
The "IN1" parameter, and connect this
to "SLOT3_F-IN3".
The "IN2" parameter is automatically
set to "SLOT3_F-IN4".
Activate cross-circuit detection.
Select the following in the "Parameter >
Start" directory:
The "Type of start" parameter, and
define this as "Monitored".
Close the window by clicking "OK".
36
Result
System Manual, 10/2008, 926 2530-02 DS 02
Modular Safety System 3RK3