Siemens OH110 Technical Manual

Siemens OH110 Technical Manual

Automatic fire
Table of Contents

Advertisement

Automatic fire detectors
OH110, OP110, HI110, HI112
Technical Manual
A6V10316298_e_en_--
2014-05-21
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens OH110

  • Page 1 Automatic fire detectors OH110, OP110, HI110, HI112 Technical Manual Building Technologies A6V10316298_e_en_-- 2014-05-21 Control Products and Systems...
  • Page 2 Legal notice Technical specifications and availability subject to change without notice. © 2012-2014 Copyright by Siemens Switzerland Ltd Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited.
  • Page 3: Table Of Contents

    Table of contents About this document ..................5 Applicable documents ..................7 Download center....................7 Technical terms ....................7 History of changes ....................8 Safety ......................9 Safety instructions ....................9 Safety regulations for the method of operation ..........11 Standards and directives complied with ............13 Release Notes ....................
  • Page 4 Performance check ..................50 Testing the point detector ................50 Specifications ....................51 Technical data for multi-sensor fire detector OH110 ........51 Technical data for smoke detector OP110 ............52 Technical data for heat detectors HI110 / HI112 ..........54 Dimensions ....................
  • Page 5: About This Document

    This document contains information on automatic fire detectors. Following the instructions consistently will ensure that the product can be used safely and without any problems. Scope The document is valid for the following automatic fire detectors: OH110 OP110 HI110 HI112 Target groups...
  • Page 6 About this document Applicable documents Reference document and source language The source language of this document is German (de). The reference version of this document is the international version in English. The international version is not localized. The reference document has the following designation: ID_x_en_-- x = version, en = English, -- = international Document identification...
  • Page 7: Applicable Documents

    List of compatibility (for 'Sinteso™' product line) A6V10201731 Installation Detector exchanger DX791, adapter for detector exchanger FDUD491 A6V10301051 Data sheet Automatic fire detectors OH110, OP110, HI110, HI112 A6V10316300 Installation Detector base (collective) DB110, DB110D, DB110R, DB110RD, detector base seal RS720, detector...
  • Page 8: History Of Changes

    2013-08-31 Information on LPCB approvals for OH110, HI110, and HI112 point detectors 2012-06-15 CPD/G number for OH110/OP110 added, new date format in line with ISO 8601 (yyyy-mm-dd) 2012-04 First edition The table below shows the published language versions with the corresponding...
  • Page 9: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger...
  • Page 10 Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
  • Page 11: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, assembly, installation,...
  • Page 12 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 13: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 14: Structure And Function

    3 Structure and function 3.1 Overview In this document the following point detectors are referred to collectively using the term 'Automatic fire detectors': Multi-sensor fire detector (collective) OH110 Smoke detector (collective) OP110 Heat detector (collective, differential) HI110 Heat detector (collective, static) HI112...
  • Page 15: Product Version Es

    Structure and function Overview 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number. You will find the details of your device's product version: On the packaging label On the product label or the type plate Product version on the packaging label...
  • Page 16: Point Detector

    Structure and function Point detector 3.2 Point detector 3.2.1 Multi-sensor fire detector The multi-sensor fire detector OH110 is a multiple-criteria fire detector with one optical and one thermal sensor. Structure and function 1 Labyrinth 3 Optical receiver 2 Optical transmitter 4 Heat sensor The point detector has a high-quality opto-electronic measuring chamber.
  • Page 17: Smoke Detector

    Structure and function Point detector 3.2.2 Smoke detector The wide-spectrum smoke detector OP110 is an optical smoke detector with one optical sensor. Structure and function 1 Labyrinth 3 Optical receiver 2 Optical transmitter The wide-spectrum smoke detector has the same measuring chamber as the multi- sensor fire detector.
  • Page 18: Heat Detector

    Structure and function Point detector 3.2.3 Heat detector The heat detectors HI110 and HI112 are pure heat detectors with one thermal sensor. The following table indicates the most important differences between the two heat detectors. Parameter HI110 HI112 Alarm activation by: Temperature increase Reaching the maximum temperature...
  • Page 19: Function

    The table below illustrates the dependency between the point detector's parameter sets and the detector bases used. Point detector Detector base Detector base used DB110 or DB110D DB110R or DB110RD OH110 'Sensitive' 'Robust' OP110 'Standard' 'Sensitive' HI110 'A1R' HI112 'A2S' 3.3.2...
  • Page 20: Internal Alarm Indicator

    When the point detector is in normal operation, the internal alarm indicator does not light up or flash. The meaning of the internal alarm indicator's flash signals is explained in the tables below. Multi-sensor fire detector OH110 Color Parameter set Flashing frequency...
  • Page 21: Connection For External Alarm Indicators

    Optical detectors can be tested with the test gas REF8 or REF8-S. Heat detectors can be tested with a hot air fan. Once the detector line has been started up or reset, the smoke detector OH110 has a reduced response time in the 'Robust' parameter set for a period of 3 minutes.
  • Page 22: Mechanical Setup

    Structure and function Mechanical setup 3.4 Mechanical setup One of the following devices is required to install a point detector: Detector base (collective) DB110 Detector base (collective) DB110D Detector base (collective) DB110R Detector base (collective) DB110RD Once the detector base (2) has been installed, the point detector (1) is easily turned by hand or with the detector exchanger DX791 in the base.
  • Page 23: Accessories

    Selects the default parameter set in the point detector used For the recess-mounted cable entry For the surface-mounted cable entry, up to 8 mm cable diameter Compatible with: – Multi-sensor fire detector OH110 – Smoke detector OP110 – Heat detector HI110 – Heat detector HI112 Order no.: S54372-F5-A1...
  • Page 24: Detector Base (Collective) Db110R

    For the recess-mounted cable entry For the surface-mounted cable entry, up to 8 mm cable diameter Compatible with: – Multi-sensor fire detector OH110 – Smoke detector OP110 – Heat detector HI110 – Heat detector HI112 Order no.: S54372-F7-A1...
  • Page 25: Designation Plate Fdbz291

    Structure and function Accessories 3.5.5 Designation plate FDBZ291 To identify the location Compatible with: – Detector base (collective) DB110 – Detector base (collective) DB110x – Detector base (collective) DB110xx Order no. A5Q00002621 See also 2 Designation plate FDBZ291 [➙ 42] 3.5.6 Detector base seal RS720 For installation in wet rooms...
  • Page 26: Base Attachment Wet Ba721

    Structure and function Accessories 3.5.8 Base attachment wet BA721 For installation in humid, wet environments and if the detector heating unit is used Protection category achievable: IP44 Six break-out points for M20 x 1.5 metal cable glands Compatible with: – Detector base DB72x/DB110xx/DB721D –...
  • Page 27: Protective Cage Dbz1194

    2 Base attachment wet BA721 [➙ 39] 3.5.13 Detector locking device LP720 For protection against theft Compatible with: – Multi-sensor fire detector (collective) OH110 – Smoke detector (collective) OP110 – Heat detector (differential, collective) HI110 – Heat detector (static, collective) HI112 Order no.: S54319-F9-A1...
  • Page 28: Micro Terminal Dbz1190-Aa

    Structure and function Accessories 3.5.14 Micro terminal DBZ1190-AA Auxiliary terminal for connecting cables For T-branches of additional cabling e.g. for detector heating units, sounder base, external alarm indicators etc. For wire diameters of 0.28…0.5 mm 4-pin Order no.: BPZ:4677080001 See also 2 Auxiliary terminals DBZ1190-AA/-AB [➙...
  • Page 29: Planning

    You will find details in the 'List of compatibility'. 4.2 Multi-sensor fire detector Like all optical smoke detectors, the multi-sensor fire detector OH110 is able to detect slow-burning fires that generate smoke. However, when compared to standard optical smoke detectors, the multi-sensor fire detector OH110 also offers improved response behavior in the event of open fires and increased resistance to misleading sources of false alarms.
  • Page 30: Specifications

    Planning Multi-sensor fire detector 4.2.2 Specifications The table below shows the properties of the parameter sets for the multi-sensor fire detector OH110: Name Thermal Typ. response Sensitivity Static activation Differential activation Differential activation time temperature temperature possible from: [%/m] [°C] ∆T [K]...
  • Page 31: Smoke Detector

    Planning Smoke detector 4.3 Smoke detector The optical smoke detector OP110 demonstrates quick response behavior in the event of slow-burning fires that generate smoke. It is extremely well suited to general-purpose applications. The smoke detector OP110 has two selectable parameter sets. 4.3.1 Parameter sets Standard:...
  • Page 32: Heat Detector

    Planning Heat detector 4.4 Heat detector The heat detector HI110 can recognize sharp increases in temperature and is suitable for areas with a stable ambient temperature. The heat detector HI112 responds when the temperature exceeds a preset threshold value. Heat detectors are used in environments where misleading sources of false alarms are present and where, if smoke detectors were to be used, an unacceptable number of false alarms would be triggered.
  • Page 33: Specifications

    Planning Heat detector 4.4.2 Specifications The table below shows the properties of the parameter sets for the heat detectors HI110 and HI112: Name Operating temperature Static activation Differential activation Differential activation typ. / max. temperature temperature possible from: [°C] [°C] ∆T [K] [°C] 'A1R'...
  • Page 34: Mounting / Installation

    Mounting / Installation Required space 5 Mounting / Installation 5.1 Required space When the point detector is inserted, the detector base is placed under stress by compression, tension, and torsion. The fastening method must, therefore, be designed accordingly. Detector bases must be placed flat on the ceiling. Avoid mounting on steps, concrete ribs, etc.
  • Page 35: Detector Base (Collective) Db110 / Db110X / Db110Xx

    Mounting / Installation Detector base (collective) DB110 / DB110x / DB110xx 5.2 Detector base (collective) DB110 / DB110x / DB110xx Install the detector base directly on the ceiling. Insert the cables into the detector base. You have the option of using the following types of line: –...
  • Page 36: Detector Base Seal Rs720

    Mounting / Installation Detector base seal RS720 5.3 Detector base seal RS720 Use the detector base seal RS720 to install point detectors in wet rooms. Protection category: IP42. Compatible with the following detector bases: – Detector base (collective) DB110 – Detector base (collective) DB110R –...
  • Page 37: Base Attachment Ba720

    Mounting / Installation Base attachment BA720 5.4 Base attachment BA720 Install the base attachment BA720 if you are using a cable with a diameter >8 mm for surface-mounted cable entry. The base attachment BA720 is attached to the ceiling together with a detector base.
  • Page 38 Mounting / Installation Base attachment BA720 Installation for surface-mounted cable entry: 1. Break out the areas required for cable entry in the base attachment BA720 (1). 2. Insert the cables into the base attachment BA720 (1) through the broken-out areas. 3.
  • Page 39: Base Attachment Wet Ba721

    Mounting / Installation Base attachment wet BA721 5.5 Base attachment wet BA721 Base attachment wet BA721 is for surface-mounted feed lines in humid and cold environments. The cables are inserted using M20 x 1.5 metal cable glands (Fig. 3). Protective cages DBZ1194/FDBZ294 can be installed on 'base attachment wet BA721'.
  • Page 40 Mounting / Installation Base attachment wet BA721 Fig. 1 Installation of base attachment wet BA721 Installation on back box on substructure (2 screws) Installation of housing cover on back box (4 screws) Installation of detector base (2 screws) Fig. 2 Master gauge for recesses Fig.
  • Page 41: Detector Locking Device Lp720

    Mounting / Installation Detector locking device LP720 5.6 Detector locking device LP720 The point detector can be protected against theft with the detector locking device LP720. The detector locking device LP720 is compatible with Detector base (collective) DB110 Detector base (collective) DB110D Detector base (collective) DB110R Detector base (collective) DB110 RD A Grub screw M3 x 12 mm...
  • Page 42: Designation Plate Fdbz291

    Mounting / Installation Designation plate FDBZ291 5.7 Designation plate FDBZ291 1. Label designation plate FDBZ291 with location address of point detector. 2. Attach designation plate FDBZ291 to detector base DB110, DB110x or DB110xx. If the detector base seal RS720 is being used, it is not possible to install the designation plate FDBZ291.
  • Page 43: Cable Entry

    Mounting / Installation Cable entry 5.8 Cable entry The detector bases DB110, DB110x and DB110xx feature four screw terminals. A maximum of 2 cables may be connected to each screw terminal. The cable cross section of the screw terminals is 0.2…1.6 mm Terminal name Connection +Connection for external alarm indicator...
  • Page 44: Detector Dust Cap

    Detector dust cap 5.9 Detector dust cap 1. Cover the point detectors OH110 and OP110 with the detector dust cap during the construction phase. This will protect the point detector from dust and dirt. 2. Once construction work is complete, remove the detector dust cap from the point detector.
  • Page 45: Detector Heating Unit Fdbh291

    Mounting / Installation Detector heating unit FDBH291 5.10 Detector heating unit FDBH291 5.10.1 Installation of the detector heating unit When the detector is exposed to icing or moisture condensation (e.g., in cooling rooms, attics, loading ramps), detector heating unit FDBH291 is installed in the detector base.
  • Page 46: Connection Of The Detector Heating Unit

    Mounting / Installation Detector heating unit FDBH291 5.10.2 Connection of the detector heating unit Connect the cables for the monitored supply from the control panel and the detector heating unit to the supplied micro terminals DBZ1190-AA. The cables can be placed in the same cable harness as the detector line or separately.
  • Page 47: Protective Cages

    Mounting / Installation Protective cages 5.11 Protective cages Protective cage DBZ1194 protects the detector against mechanical damage. EMC-protective cage FDBZ294 protects the detector against mechanical damage and electromagnetic fields. 5.11.1 Installation of the protective cages The protective cages can only be installed on the base attachment wet FDB295. Installation of the protective cages 1 Base attachment 4 Flat plug 6.3 x 0.8 mm...
  • Page 48: Connection Diagram

    Mounting / Installation Connection diagram 5.12 Connection diagram Cables and topology The connection is established from detector base to detector base using twisted or untwisted wire pairs. Wherever possible use twisted, unshielded cables. Shielded cables are only required in special cases, such as strong high- frequency fields.
  • Page 49: Commissioning

    Commissioning 6 Commissioning The devices are commissioned via the control panel. The exact procedure is described in the control panel documentation. Building Technologies A6V10316298_e_en_-- Fire Safety 2014-05-21...
  • Page 50: Maintenance / Repair

    REF8 Hot air fan Once the detector line has been started up or reset, the smoke detector OH110 has a reduced response time in the 'Robust' parameter set for a period of 3 minutes. It is possible to test the point detector with test gas during this period.
  • Page 51: Specifications

    = 25 °C Air pressure = 1000 hPa (750 Torr) 8.1 Technical data for multi-sensor fire detector OH110 You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable...
  • Page 52: Technical Data For Smoke Detector Op110

    Specifications Technical data for smoke detector OP110 Ambient conditions -10…+50 °C Operating temperature/permissible ambient temperature Storage temperature -30…+70 °C Air humidity ≤95 % rel. Protection categories according to EN 60529 / IEC 60529: Bases DB110, DB110x, DB110xx IP40 (all installation types) Bases DB110, DB110x, DB110xx IP42 with detector base seal RS720...
  • Page 53 Specifications Technical data for smoke detector OP110 Device characteristics Response sensitivity 1.8 or 2.5 %/m (depending on the parameter at 0.2 m/s (typ.) set) Permissible wind speed Max. 5 m/s Compensation speed ≤1/45 voltage increase for detection/h Flashing interval times AI: See chapter 'Internal alarm indicator' Connections Detector line and external alarm...
  • Page 54: Technical Data For Heat Detectors Hi110 / Hi112

    Specifications Technical data for heat detectors HI110 / HI112 8.3 Technical data for heat detectors HI110 / HI112 You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: Document A6V10301051 Detector line...
  • Page 55 Specifications Technical data for heat detectors HI110 / HI112 Ambient conditions Operating temperature/permissible ambient temperature: HI110 -10…+50 °C HI112 with 'A2S' parameter set -10…+50 °C HI112 with 'B' parameter set -10…+65 °C Storage temperature -30…+70 °C Air humidity ≤95 % rel. Protection categories according to EN 60529 / IEC 60529: Bases DB110, DB110x, DB110xx...
  • Page 56: Dimensions

    Dimensions 8.4 Dimensions OH110 OP110 HI110, HI112 OH110 with base OP110 with base HI110, HI112 with base 8.5 Environmental compatibility and disposal This device is manufactured using materials and procedures which comply with current environmental protection standards as best as possible.
  • Page 57: Index

    Index Index Environmental compatibility, 56 Alarm indicator External, 21 Product version, 15 Approvals, 51, 52, 54 EU directives, 51, 52, 54 Auxiliary terminals External alarm indicators, 21 Connection terminal, 43 Micro terminal, 43 Heat detector, 18 Differential, 14 Cables, 48 Static, 14 CE marking, 51, 52, 54 Hot air fan, 50...
  • Page 58 Index Test gas REF8, 50 REF8-S, 50 Test mode, 21 Testing equipment Hot air fan, 21, 50 Test gas, 50 Test gas REF8, 21 Test gas REF8-S, 21 Topology, 48 Type plate Product version, 15 Wide-spectrum smoke detector, 17 Building Technologies A6V10316298_e_en_-- Fire Safety 2014-05-21...
  • Page 59 Index Building Technologies A6V10316298_e_en_-- Fire Safety 2014-05-21...
  • Page 60 Issued by © 2012-2014 Copyright Siemens Switzerland Ltd Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID...