Data Set 0; General Data Set 0; Data Set 0 In Mss Central Unit - Siemens Sirius 3RK3 System Manual

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Diagnostics / service
8.5 Diagnostics with data sets
8.5.3

Data set 0

8.5.3.1

General data set 0

This DS is available for both the central unit and the DP interface. DS0 in the central unit can
be queried via DP slot number 1 on the PROFIBUS slot model, and DS0 in the DP interface
can be queried via DP slot number 0.
8.5.3.2

Data set 0 in MSS central unit

The content of DS0 for the MSS central unit is described below:
Byte no.
0
1
2
3
274
Coding
Meaning
Bit 0 = 1
Module fault
Bit 1 = 1
Internal error
Bit 2 = 1
External error
Bit 3 = 1
Channel error
Bit 4 = 1
No external auxiliary supply
Bit 5 = 1
No front panel connector
Bit 6 = 1
Module not parameterized
Bit 7 = 1
Incorrect parameters in device
Bits 0...3
Type class
Bit 4 = 1
Channel information available
Bit 5 = 1
User information available
Bit 6 = 0
Diagnostic interrupt from
substitute
Bit 7 = 0
reserved
Bit 0 = 1
No user module / user module
incorrect
Bit 1 = 1
Communication fault
Bit 2 = 0 RUN
RUN / STOP status
Bit 2 = 1 STOP
Bit 3 = 1
Time monitoring
Bit 4 = 1
Module supply failed
Bit 5 = 1
Battery empty
Bit 6 = 1
Entire buffering failed
Bit 7 = 1
reserved
Bit 0 = 1
Rack failure
Bit 1 = 1
Processor failure
Bit 2 = 1
Memory module error
Bit 3 = 1
RAM error
Bit 4 = 1
ADU/DAU error
Comments
SF on central unit
Device error on central unit
Logic or wiring error
Not supported
Not supported
Not supported
No configuration saved in device
Incorrect configuration saved in
device
0000 CPU
DS1 exists
Always 1 for MSS because
diagnostics information is available
via DS92
Always 0 for MSS
-
Configuration error in MSS TARGET
/ ACTUAL
Error on SafetyConnect
RUN: MSS in safety/test mode
STOP: MSS in configuring mode
Cycle time violation of MSS
Not supported
Not supported
Not supported
-
SafetyConnect failed
Not supported
Error in external memory module
Not supported
Not supported
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02