Description of the software
6.7 Functions
6.7.6.6

NEGATION (NEG)

Description
The logic operation "NEGATION" has one input IN and one function output Q for the result of
logic operation (RLO).
An inverted input signal is output at the function output Q.
RLO = 1 when input IN has the status "0".
Parameters
Parameter name
General
Name
Element number
Element activated
Function output substitute
value
186
Description/parameter value
You can enter a name for the element here.
Consecutive number which is automatically assigned. You can change
the number.
When this parameter is active, the function is processed in the safety
logic.
When this parameter is deactivated, the set substitute value is made
available at the output Q.
"0" or "1" can be assigned to the substitute value when the element is
deactivated.
Substitute value "0" means output Q = 0
substitute value "1" means output Q = 1
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02