Description of the software
6.4 Description of the menu commands
6.4.3.10

Commands...

Activate device commands
Using the "Target system" > "Commands" menu command, you can activate additional
functions on the safety relay.
1. Select a command from the drop down list in the dialog box.
2. Send it to the safety relay via the "Send" button.
You can start another command once the previous command is executed and the "Send"
button is active again.
Observe the current status
A list in the "Commands" dialog box shows the current status of the command processing
and the feedback messages from the diagnostics data memory determined by the MSS ES
safety relay. The list is expanded with each sent command. It is deleted when the dialog box
is closed.
Device commands
The following device commands are available:
Device
Description
commands
Factory settings
All of the parameter values are reset to
their default values.
After the factory settings have been
restored, the device executes a restart
autonomously, the connection to the
safety relay is interrupted, and the
configuration is closed.
Reset
Tripping, i.e. a shutdown due to a
protection violation, can be
acknowledged using this command. All
of the faults whose causes have been
eliminated are acknowledged together
Restart
Causes a "HW reset" of the safety relay.
116
Can be activated in
Feedback
Configuring
Factory settings restored
mode
The restart is executed.
Configuring
Reset implemented.
mode
Reset not possible.
Test mode
Safety mode
Configuring
The restart is carried out.
mode
Test mode
Safety mode