Description of the software
6.4 Description of the menu commands
6.4.3

Target system menu

6.4.3.1

Load to switching device...

The menu command "Target system" > "Load to switching device" saves the parameters of
the current configuration to a safety relay via an online connection.
Note
Overwriting the parameters
When you choose this menu command, the parameters in the safety relay are overwritten
without you being prompted to confirm this.
Transferring the parameters
Transfer the parameters as follows:
● Open an online connection to a safety relay via the connection dialog box.
● Click "OK" to close the dialog box.
● The program establishes a connection with the specified safety relay, checks whether the
parameters that are currently displayed are compatible with this safety relay, and then
loads all the parameters to the safety relay.
6.4.3.2

Load to PC...

The menu command "Target system" > "Load to PC" downloads the parameters currently
stored in the safety relay to the PC via an online connection.
Note
Overwriting the parameters
When you choose this menu command, the parameters in the main memory are immediately
overwritten.
Transferring the data
Transfer the data as follows:
● Open an online connection to a safety relay via the connection dialog box.
● Click "OK" to close the dialog box.
● The program establishes a connection with the specified switching device and reads all
parameters from the device to the PC.
6.4.3.3

Go offline

The menu command "Target system" > "Go offline" terminates an existing online connection
to a switching device.