Siemens Sirius 3RK3 System Manual page 45

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Structure of the 3RK3 Basic central unit
Terminal names of the 3RK3 Basic central unit
Terminal
T1
T2
IN1 ... IN8
Q1.1, Q1.2
Q2
L+
M
FE
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
Front view
Meaning
Test output for inputs IN1,
IN3, IN5, IN7
Test output for inputs IN2,
IN4, IN6, IN8
Safety-related sensor inputs Connection for safety sensors
Safety-related relay output
Safety-related solid-state
output
Power supply
Ground
Functional ground
5.1 Description of the individual modules
No.
Meaning
(1)
Removable terminal block D
(2)
Removable terminal block C
(3)
Connection to expansion module
(4)
RESET button
(5)
Removable terminal block A
(6)
Connection of memory module
(7)
Inscription label
(8)
Display LEDs
(9)
Connection of PC / PG / communications
module
Description
Test outputs with different test signals
Connection for sensor contacts for detecting cross-
circuits
Combinations for two-channel connection method:
IN1-IN2, IN3-IN4, IN5-IN6, IN7-IN8
Isolated, redundant output for connecting actuators
Redundant semiconductor output for connecting
actuators
24 V DC
Ground to 24 V DC
Shielding, equipotential bonding
Description of the hardware
43