9.5 Climatic ambient conditions

9.5
Climatic ambient conditions
9.5.1

Transport and storage conditions

The following information applies to an HMI device and connection box transported and
stored in their original packaging.
The HMI device meets the requirements of IEC 60721-3-2, Class 2K2 with the following
amendments and limitations:
Type of condition
Temperature
Atmospheric pressure
Relative humidity
Pollutant concentration
Note
• Ensure that no condensation (dewing) develops on or inside the HMI device after
transporting it at low temperatures or after it has been exposed to extreme temperature
fluctuations.
• The HMI device must have acquired room temperature before it is put into operation. Do
not expose the HMI device to direct radiation from a heater in order to warm it up. In case
of condensation, wait until the HMI device has dried completely or approximately 4 hours
before switching it on.
9.5.2

Operating Conditions

The HMI device is designed for mobile operation in a location protected from the weather.
The HMI device meets the requirements of IEC 60721-3-3, Class 3K3 with the following
amendments and limitations:
The following information applies to the HMI device and to the connection box.
Type of condition
Temperature, HMI device
Temperature, connection boxes 0 ... 55 °C
Atmospheric pressure
Relative humidity
Pollutant concentration
160
Permitted range
-20 ... +60 °C
1080 ... 660 hPa, corresponds to an elevation of 1000 m to 3500 m
10 ... 90%, without condensation
SO2: < 0.5 ppm; Relative humidity < 60%, no condensation
H
S: < 0.1 ppm; Relative humidity < 60%, no condensation
2
Permitted range
0 ... 45 °C
1080 ... 795 hPa, corresponds to an elevation of 1000 m to 2000 m
10 ... 90 %, no condensation
SO
: < 0.5 ppm; Relative humidity < 60%, no condensation
2
H
S: < 0.1 ppm; Relative humidity < 60%, no condensation
2
Operating Instructions, 08/2017, A5E39831415-AA