4.2

Operating the enabling button

The enabling mechanism comprises one integrated enabling button with three settings.
The signals of the enabling button are evaluated internally and sent to the connection box
over the connecting cable. For setup mode, these signals must be wired dual-channel from
the connection box to the F-system.
Requirement
● The HMI device is connected to a correctly installed connection box.
Procedure
1. Press the enabling key to switch position 2 or 3.
– The figure below shows the switching sequence for normal operation.
– The figure below shows the switching sequence for panic operation.
2. Release the enabling button.
If the enabling button is in switch position "3", the "Enable" setting is skipped when the
button is released.
Note
Releasing the enabling button and the "Panic" switch position do not require
acknowledgement of the safety shutdown.
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
Switch position
1
2
3
4.2 Operating the enabling button
Function
Neutral position
Enable
Panic
Handling the Mobile Panel
Enabling button switch status
Opened
Closed
Opened
67