Safety instructions
2.4 Important information on emergency stop / stop button
Stop functions of Category 0 or 1 according to EN 60204-1
If a category 0 or 1 stop circuit is implemented, the stop function must be effective
regardless of the operating mode. A category 0 stop must take precedence. Releasing the
emergency stop / stop button must not lead to any dangerous state (see also EN 60204-1,
Section 9.2.5.3).
The stop function is not to be used as a replacement for safety equipment.
Hardwired F-system
The emergency stop / stop button can trigger a safe machine stop or be looped into the
safety circuit of the F-system based on the configuration of the F-system. The signals of the
emergency stop / stop button are wired differently in the connection boxes:
● For connection box compact and connection box standard: When the fail-safe Mobile
Panel is not connected, the safety circuit is open.
● For the connection box advanced: When the fail-safe Mobile Panel is not connected, the
connection of the safety circuit is bypassed and thus closed.
NOTICE
Versions of the connection box
If you install connection boxes with and without emergency stop / stop bypass in your fail-
safe automation system, there is a risk that an accidental shutdown is triggered when
replugging an HMI device.
In a fail-safe automation system, you should therefore only use "compact" and "standard"
connection boxes together or "advanced" boxes only.
See also
Assigning a safety-related operating mode (Page 115)
Pressing the emergency stop / stop button (Page 68)
32
WARNING
NOTICE
Emergency stop / stop bypass only works with fail-safe operator panel
If you use a non-fail-safe HMI device with the connection box advanced and remove it
from the connection box advanced, the safety circuit is opened and the relevant plant
section or the plant goes into a safe state.
Only use fail-safe Mobile Panels in conjunction with the connection box advanced in an
F-system with emergency stop / stop bypass.