Parameterizing the Mobile Panel
5.13 Functions for service and commissioning
Using system memory card with automatic backup, project data on the device
NOTICE
Data loss
All data on the HMI device, including the project and HMI device password, is deleted
during a restore operation. License keys are only deleted after a security prompt.
Back up your data before the restore operation, if necessary.
1. In the "Service & Commissioning" dialog, "Automatic Backup" tab, check whether the
"Automatic Backup" function is enabled.
– If the function is enabled, close the dialog.
– If the function is not enabled, press the "Enable & Reboot" button.
2. Insert the SIMATIC HMI Memory Card with automatic backup into the slot for the system
memory card.
If the system memory card was recognized and read, the "Use system card" dialog is
displayed as follows:
3. Select the "Start backup" check box in order to create a backup of the device data on an
external storage medium before the device data is overwritten by the data on the system
memory card. Select the corresponding path and file name under "Medium:".
4. Press the "Continue" button. If the "Start backup" check box was selected, the device
then creates a corresponding data backup.
The data of the system memory card is then transferred to the HMI device.
After the data transfer, the state of the HMI device is the same as that of the HMI device
used to generate the automatic backup.