Maintenance And Care; Replacing The Mobile Panel; Servicing The Mobile Panel - Siemens SIMATIC HMI TP1000F Mobile RO Operating Instructions Manual

Table of Contents

Advertisement

Maintenance and care

8.1

Replacing the Mobile Panel

When replacing an HMI device, the following applies:
● The TP1000F Mobile RO can only be replaced with a device of the same design.
● For a 1:1 data transfer from one HMI device to another, a replacement device with
identical construction is required.
Below you will find a description of how to replace an HMI device with a replacement device
with identical construction.
Replacement device with identical construction, manual backup exits
1. Insert the storage medium with the manually created backup into the slot of a
replacement device with identical construction.
2. Proceed as described in the section "Functions for service and commissioning
(Page 117)".
See also
Unplugging the connecting cable (Page 150)
8.2

Servicing the Mobile Panel

The HMI device is designed for low-maintenance operation. Also take into account the
system components and accessories when carrying out maintenance. For maintenance,
follow the safety instructions in "General safety instructions (Page 25)".
The scope of maintenance includes the following function tests:
● Function test of enabling button
● Function test of emergency stop / stop button
Depending on the Safety Integrity Level SIL of your application, the function tests are
performed at the following intervals.
● SIL2: 1 x annually
● SIL3: 1 x monthly
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA