Reaction times
The table shows below the reaction times of the HMI device up to the output or interface X10
of the connection box, dependent on the F-system.
Reaction time
Emergency stop / stop button
Reaction time during error-free
operation
Reaction time with error
Discrepancy time
Acknowledgment time in safety mode
Enabling
Reaction time during error-free
operation
Reaction time with error pending Discrepancy detected (safe state)
Discrepancy time
Acknowledgment time in safety mode
Note
Times
The specified times do not include the applicable safety relay.
Safety characteristics
Note
All values for the following information are based on the SN 29500:2005 and an ambient
temperature of 60 °C.
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
Operating mode
Press switch
Unlock switch
Discrepancy detected (safe state)
Critical internal error
No Enabling or Panic
Enabling
Critical internal error
Technical specifications
9.7 Technical specifications
Stop/E-stop button evaluated
by safety relay
< 10 ms
< 10 ms
See Safety relay
< 30 ms
See Safety relay
< 15 ms
< 40 ms
< 15 ms
< 30 ms
500 ms
-
171