Safety instructions
2.1 General safety instructions
NOTICE
Exclusive operating right
Operating the plant with multiple HMI devices simultaneously can cause material damage.
Prevent simultaneous operation of the plant from multiple devices by configuring the
assignment of operating rights to only one HMI device.
Configuration of fail-safe Mobile Panels
Personal injury or property damage in case of remote control of a fail-safe HMI device
The remote control of a fail-safe unit consisting of HMI devices with RemoteOperate Client
and a RemoteOperate server is not permitted because it is not ensured that the hazardous
location is visible during operation. This can result in personal injury or property damage.
The following therefore applies to the fail-safe unit (RemoteOperate Clients /
RemoteOperate Server): Remote control, for example, by means of Telnet or Sm@rtClient
is not permitted.
Personal injury or material damage with different operating modes in a plant area
If you assign different operating modes to the connection boxes in a contiguous plant area,
the emergency stop / stop button may light at one of the connection boxes but not at
another. When the emergency stop / stop button does not light up, it is not apparent to the
operator if the safety-related operator controls are active or not. This can result in personal
injury or material damage due to maloperation.
Only configure a single operating mode for multiple connection boxes in a contiguous plant
area.
Operational safety in the plant
Short-term PROFINET IO interruptions possible when using protocols with alternative
communication paths
The following applies when you use a protocol with alternative communication paths, for
example, MRP, STP or RSTP, for PROFINET communication: When an interruption in the
network occurs, for example, due to a cable break, PROFINET IO interruptions can occur
during the switching time to the alternative communication path. This can result in personal
injury or material damage.
Take appropriate protection measures to prevent physical injury or material damage.
You can find additional information in the following document:Configuration manual
"SCALANCE X-200" (https://support.industry.siemens.com/cs/ww/de/view/109476763)