Installing system components
3.6 Connecting the connection box
Requirement
● For connection box standard and connection box advanced: The connection box is open.
● The connection box is disconnected from its power supply.
● A suitable tool made of plastic
Procedure
1. Rotate the arrows of the rotary coding switch to the required hexadecimal value using a
suitable tool.
Values from "00" to "FF" (0 to 255 in decimal form) can be set with the rotary coding
switches.
When setting the box ID:
– Use the value "00" only for the "Stop button evaluated by safety relay" operating
– The value "FF" (255) is reserved and may not be used.
Example:
The figure below shows an example of the rotary coding switch for a connection box
standard. "27H" (39 in decimal form) is set for the box ID as an example.
2. For connection box standard and connection box advanced:
When all the required work has been completed in the connection box, close it.
See also
Assigning a safety-related operating mode (Page 115)
Parameterizing the Mobile Panel (Page 73)
62
mode.
Rotary encoding switch for more significant bits
This is the lower rotary coding switch in the connection box compact and the left rotary
coding switch in the connection boxes standard and advanced.
Rotary encoding switch for less significant bits
Operating Instructions, 08/2017, A5E39831415-AA
TP1000F Mobile RO