Siemens SIMATIC HMI TP1000F Mobile RO Operating Instructions Manual page 52

Table of Contents

Advertisement

Installing system components
3.6 Connecting the connection box
3. Remove the screws and the cover.
The following protective cover is visible:
Close
Follow the steps for opening in reverse order.
NOTICE
Permissible torque
The connection box enclosure is made of plastic. Therefore, the mounting hole threads
cannot handle the same amount of stress as a comparable metallic enclosure. If the screws
are tightened with too great a torque or more than 20 times, there is risk of damage to the
thread.
Do not exceed the maximum permissible torque of 0.4 – 0.5 Nm when tightening the
screws.
Note
During assembly, make sure that the seal for the cover is inserted and not damaged.
Otherwise degree of protection IP65 is not ensured.
52
Protective cover
NOTICE
Damage to the connection box
Without a protective cover, there is a risk that the electronics of the connection box are
damaged or destroyed.
Do not remove the protective cover.
Operating Instructions, 08/2017, A5E39831415-AA
TP1000F Mobile RO