Server time

To obtain the time of the HMI device from a time server, you can specify up to four different
time servers. The time is synchronized using the "Network Time Protocol". The
synchronization cycle applies to all configured time servers.
Requirement
● The HMI device and time server are located in the same network.
● The Control Panel is open.
Procedure
1. Open the "PROFINET" dialog using the "PROFINET" icon.
2. Change to the "NTP" tab.
3. If you want to use the time of a time server, activate "Automatically synchronize with ...".
4. Under "Update rate", enter the time interval in seconds after which the HMI device is to
synchronize the time.
Permitted value range: 1 ... 60 000 000 seconds.
5. Press the "Configure" button.
The following dialog is displayed:
If you do not enter a time, the message "Second field wrong data type." will appear. Enter
a time.
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
Text box for time servers 1 to 4
Button for configuring the time servers
Parameterizing the Mobile Panel
5.10 Server time
109