Technical specifications
9.3 Electromagnetic compatibility
Disturbance variables
Electromagnetic compatibility applies for the following types of disturbance variables:
● Pulse-shaped disturbance variables
The table below shows the electromagnetic compatibility of the Mobile Panel and the
connection boxes with regard to pulse-shaped disturbance variables.
An external safety circuit is required for the "Surge immunity test according to IEC 61000-
4-5".
● Sinusoidal interference
The table below shows the electromagnetic compatibility of the Mobile Panel and the
connection boxes with regard to sinusoidal interference.
The following table shows the unwanted emissions from electromagnetic fields in
accordance with EN 55016, Limit Value Class A, Group 1, measured at a distance of
10 m.
Emission of radio interference
Before you connect the HMI device and any connection box to the public electricity network,
you must make sure that they comply with Limit Value Class B in accordance with EN
55022.
158
Pulse-shaped disturbance
Electrostatic discharge
in accordance with IEC 61000-4-2
Burst pulses
(high-speed transient interference)
in accordance with IEC 61000-4-4
Pulse-shaped disturbance
Asymmetrical coupling
Symmetrical coupling
Sinusoidal interference
HF radiation (in electromagnetic
fields) in accordance with
IEC 61000-4-3
RF interference current on cables
and cable shielding conforming to
IEC 61000-4-6
30 to 230 MHz
230 to 1 000 MHz
Tested with
Air discharge: 8 kV
Contact discharge: 6 kV
2 kV supply line
Tested with
2 kV power cable
DC voltage with protective elements
1 kV power cable
DC voltage with protective elements
Test values
80% amplitude modulation at 1 kHz
Up to 10 V/m in the 80 MHz to 1 GHz range
Up to 10 V/m in the 1.4 GHz to 2 GHz
range
Up to 3 V/m in the 2 GHz to 6 GHz range
Test voltage 10 V, with 80% amplitude
modulation of 1 kHz in the 9 kHz to 80 MHz
range
< 40 dB (V/m) quasi-peak
< 47 dB (V/m) quasi-peak
Operating Instructions, 08/2017, A5E39831415-AA
Degree of
severity
3
3
Degree of
severity
3
3
Degree of
severity
3
3
TP1000F Mobile RO