9.7.6

Specification of cables to be used

Cables for 24 V DC and functional grounding
Connectable cable cross-sections for single-
core/solid cables H05(07) V-U
Connectable cable
cross-sections for
flexible/stranded
cables
H05(07) V-K
Number of cables per connection
Stripped length of the cables
Connection technology
Connections for emergency stop / stop button
and enabling button
Connectable cable cross-sections for single-
core/solid cables H05(07) V-U
Connectable cable
cross-sections for
flexible/stranded
cables
H05(07) V-K
Number of cables per connection
Stripped length of the cables
Connection technology
PROFINET cables
Connectable cable
Connection technology
* Available on the Internet at: Industrial Ethernet FastConnect Cable 2x2
(http://w3.siemens.com/mcms/industrial-communication/en/ie/Cabling-technology/fc-cable-
2x2/Pages/fc-cable-2x2.aspx)
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
Without ferrule
With ferrule according to
DIN 46 228/1
With ferrule according to
DIN 46 228/4
Without ferrule
With ferrule according to
DIN 46 228/1
With ferrule according to
DIN 46 228/4
Connection box
advanced
6XV1840-2AH10 or comparable
Fast connect
9.7 Technical specifications
Connection box
Connection box
advanced
standard
0.5 ... 1.5 mm²; AWG 21 ... AWG 16
0.5 ... 1.5 mm²
AWG 21 ... AWG 16
0.5 ... 1.5 mm²
0.5 ... 0.75 mm²
1
8 mm
Push-in terminal
Connection box
Connection box
advanced
standard
0.2 ... 1.5 mm²; AWG 24 ... AWG 16
0.2 ... 1.5 mm²
AWG 24 ... AWG 16
0.25 ... 1.5 mm²
0.25 ... 0.75 mm²
1
8 mm
Push-in terminal
Connection box
Connection box compact
standard
6XV1840-2AH10 or
comparable, Industrial Ethernet
FastConnect Cable 2x2 *
RJ45
Technical specifications
Connection box
compact
Connection box
compact
173

Advertisement

Table of Contents
loading