Configure device options and preferences
Restriction
Response Time is available only on systems with the enhanced core processor.
Procedure
Set Response Time as desired.
Option
Normal (Legacy)
Special (Legacy)
Normal - Optimal Filtering
Low Filtering - Fastest Re-
sponse
High Filtering - Smoothest
Output
Service
5.5

Configure alert handling

The alert handling parameters control the transmitter's response to process and device
conditions.
5.5.1

Configure Fault Timeout

Display
ProLink III
Field Communicator Configure > Alert Setup > Alert Severity > Fault Timeout
Overview
Fault Timeout controls the delay before fault actions are performed.
Restriction
Fault Timeout is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005,
A008, A016, A017, A033. For all other alerts, fault actions are performed as soon as the alert is
detected.
62
Description
Transmitter calculates process variables at the standard speed. This op-
tion is selected if this parameter was configured on an earlier version of
ProLink III software.
Transmitter calculates process variables at a faster speed. This option is
selected if this parameter was configured on an earlier version of ProLink
III software.
Transmitter calculates process variables at standard filtering and speed.
Transmitter calculates process variables at the fastest speed.
Transmitter calculates process variables at the smoothest (least noisy)
response to changes in the process.
For factory use only.
Not available
Device Tools > Configuration > Fault Processing