Configure Response Time - Emerson Micro Motion 1700 Configuration And Use Manual

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1700:
Table of Contents

Advertisement

Effects of Update Rate = Special
Incompatible features and functions
Special mode is not compatible with the following features and functions:
If required, you can switch to Normal mode, perform the desired procedures, and then
return to Special mode.
Process variable updates
Some process variables are not updated when Special mode is enabled.
Table 5-1:
Special mode and process variable updates
Always polled and updated
Mass flow
Volume flow
Gas standard volume flow
Density
Temperature
Drive gain
LPO amplitude
Status [contains Event 1 and Event
2 (basic events)]
Mass total
Volume total
Live zero
Gas standard volume total
5.4.2

Configure Response Time

Display
ProLink III
Field Communicator Not available
Overview
Response Time is used to apply a different algorithm to the calculation of process variables
from the raw process data.
Configuration and Use Manual
Enhanced events. Use basic events instead.
All calibration procedures.
Zero verification.
Restoring the factory zero or the prior zero.
Updated only when the petroleum
measurement application is disa-
bled
RPO amplitude
Core input voltage
Mass inventory
Volume inventory
Gas standard volume inventory
Not available
Device Tools > Configuration > Process Measurement > Response > Response Time
Configure device options and preferences
Never updated
All other process variables and calibra-
tion data. They retain the values held
at the time you enabled Special mode.
61