Emerson Micro Motion 1700 Configuration And Use Manual page 213

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1700:
Table of Contents

Advertisement

CAUTION!
If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals.
Connecting directly to the transmitter terminals requires opening the wiring compartment,
and opening the wiring compartment while the transmitter is powered up could cause an
explosion. To connect to the transmitter in a hazardous environment, use a connection
method that does not require opening the wiring compartment.
CAUTION!
If you connect directly to the mA terminals, the transmitter's mA Output may be affected. If
you are using the mA Output for process control, set devices for manual control before
connecting directly to the mA terminals.
Prerequisites
Procedure
1.
2.
Configuration and Use Manual
ProLink III is installed and licensed on your PC
One of the following:
-
RS-232 to Bell 202 signal converter
-
USB to Bell 202 signal converter
An available serial port or USB port
Adapters as required (for example, 9-pin to 25-pin)
Attach the signal converter to the serial port or USB port on your PC.
To connect directly to the transmitter terminals:
a. Remove the transmitter end-cap to access the wiring compartment.
b. Connect the leads from the signal converter to terminals 1 and 2.
Tip
HART connections are not polarity-sensitive. It does not matter which lead you attach to
which terminal.
c. Add resistance as necessary to achieve at least one volt across the connection
points.
Important
HART/Bell 202 connections require a voltage drop of 1 VDC. To achieve this, add
resistance of 250–600 Ω to the connection.
Using ProLink III with the transmitter
205