Integrate the meter with the control system
Table 6-4:
Valid values for Added Damping
Setting of Update Rate
Interaction between mA Output Damping and process
variable damping
When mA Output Source is set to a flow rate variable, mA Output Damping interacts with
Flow Damping. If multiple damping parameters are applicable, the effect of damping the
process variable is calculated first, and the mA output damping calculation is applied to
the result of that calculation.
Example: Damping interaction
Configuration:
Result: A change in the mass flow rate will be reflected in the mA Output over a time
period that is greater than 3 seconds. The exact time period is calculated by the
transmitter according to internal algorithms which are not configurable.
6.2.5
Configure mA Output Fault Action and mA Output Fault
Level
Display
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output > MA0 Fault Settings
Overview
mA Output Fault Action controls the behavior of the mA Output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement
the fault action until the timeout has elapsed.
78
(continued)
Process variable
100 Hz variable (if not as-
signed to the mA Output)
All other process variables
Flow Damping = 1 second
mA Output Source = Mass Flow Rate
mA Output Damping = 2 seconds
Not available
Device Tools > Configuration > Fault Processing
Update rate
in effect
Valid values for Added Damping
6.25 Hz
0.0, 0.32, 0.96, 2.40, 5.12, 10.56, 20.8, 43.2, 88,
176, 352
Micro Motion Model 1700 Transmitters with Analog Outputs