Emerson Micro Motion 1700 Configuration And Use Manual page 165

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1700:
Table of Contents

Advertisement

Alert num-
ber
Alert title
A108
Basic Event 1 On
A109
Basic Event 2 On
A110
Frequency Output
Saturated
A111
Frequency Output
Fixed
A112
Upgrade Transmit-
ter Software
A113
mA Output 2 Satura-
ted
Configuration and Use Manual
Possible cause
The process has triggered Basic
Event 1.
The process has triggered Basic
Event 2.
The calculated Frequency Output is
outside the configured range.
The Frequency Output has been
configured to send a constant val-
ue.
The transmitter software is down-
level from the core processor soft-
ware.
The calculated mA Output value is
outside the configured range.
Recommended actions
No action required.
Review event configuration if you be-
lieve the event was triggered errone-
ously.
No action required.
Review event configuration if you be-
lieve the event was triggered errone-
ously.
Check the Frequency Output scaling.
Check process conditions. Actual condi-
tions may be outside the normal condi-
tions for which the output is config-
ured.
Check for air in the flow tubes, tubes
not filled, foreign material in the tubes,
coating in the tubes, or other process
problems.
Verify that the measurement units are
configured correctly for your applica-
tion.
Purge the sensor tubes.
Cycling power to the meter or restart-
ing totalizers will restore the Frequency
Output to normal operation.
Check whether the output is in loop test
mode. If it is, unfix the output.
Check whether the output has been set
to a constant value via digital communi-
cation.
Contact customer support.
Check the settings of Upper Range Val-
ue and Lower Range Value.
Check process conditions. Actual condi-
tions may be outside the normal condi-
tions for which the output is config-
ured.
Check for air in the flow tubes, tubes
not filled, foreign material in the tubes,
coating in the tubes, or other process
problems.
Verify that the measurement units are
configured correctly for your applica-
tion.
Purge the sensor tubes.
Troubleshooting
157