Emerson Micro Motion 1700 Configuration And Use Manual page 222

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1700:
Table of Contents

Advertisement

Using ProLink III with the transmitter
Figure B-8:
Connection over network
A
A. Computer
B. Signal converter
Ω , 1/2‐watt resistors at both ends of the segment, if necessary for noise suppression
C. 120-
D. DCS or PLC
E. Transmitter, with wiring compartment and power supply compartment opened
Note
This figure shows a serial port connection. USB connections are also supported.
4.
5.
6.
7.
214
Start ProLink III.
Choose Connect to Physical Device.
Set the connection parameters to the values configured in the transmitter.
If your transmitter has not been configured, use the default values shown here.
Table B-2:
Default Modbus/RS-485 connection parameters
Parameter
Protocol
Baud
Parity
Stop Bits
Address
Tip
If you do not know the transmitter's RS-485 communication settings, you can connect
through the service port, which always uses default settings, or use another communications
tool to view or change the settings.
Set the PC Port value to the PC COM port that you are using for this connection.
D
C
B
Default value
Modbus RTU
9600
Odd
1
1
Micro Motion Model 1700 Transmitters with Analog Outputs
E

Advertisement

Table of Contents
loading

Table of Contents