Configure security for the display menus

Display
ProLink III
Field Communicator Configure > Manual Setup > Display > Offline Variable Menu Features
Overview
You can control operator access to different sections of the display off-line menu. You can
also configure a password to control access.
Procedure
1.
2.
58
Ensure that the alert menu is accessible from the display.
To acknowledge alerts from the display, operators must have access to the alert
menu.
Enable or disable Acknowledge All Alerts as desired.
Option
Description
Enabled (default) Operators can use a single display command to acknowledge all alerts at
once.
Disabled
Operators cannot acknowledge all alerts at once. Each alert must be ac-
knowledged separately.
OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY
Device Tools > Configuration > Transmitter Display > Display Security
To control operator access to the maintenance section of the off-line menu, enable
or disable Off-Line Menu.
Option
Description
Enabled (de-
Operator can access the maintenance section of the off-line menu. This ac-
cess is required for configuration and calibration, but is not required to
fault)
view alerts or to access Smart Meter Verification (if applicable).
Disabled
Operator cannot access the maintenance section of the off-line menu.
To control operator access to the alert menu, enable or disable Alert Menu.
Option
Description
Enabled (default) Operator can access the alert menu. This access is required to view and
acknowledge alerts, but is not required for Smart Meter Verification (if
applicable), configuration, or calibration.
Micro Motion Model 1700 Transmitters with Analog Outputs