11.6

Error Code List

I/O module specific error

I/O module specific error codes are as follows.
Error code
Error type
0010H
Major error
0101H
Moderate
error
0201H
Minor error
0202H
Minor error
0203H
Minor error

CC-Link IE Field Network Basic related error

For CC-Link IE Field Network Basic related error codes, refer to the manual for respective series.
 MELSEC iQ-R CPU Module User's Manual (Application)
 MELSEC iQ-F FX5 User's Manual (Application)
 QCPU User's Manual (Hardware Design, Maintenance and Inspection)
 MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and Inspection)
Error name
Description and cause
Hardware error
Module hardware error
IP address setting
An IP address setting switch is set
switch setting out of
outside the range between 0 and
range error
254.
IP address setting
An IP address setting switch has
switch changed error
been changed with the module
power supply on.
Function setting
The function setting switch 1 to 3
switch 1 to 3 changed
has been changed with the
error
module power supply on.
Function setting
The function setting switch 4 has
switch 4 changed
been changed with the module
error
power supply on.
Action
Power off and on the module power supply.
If this error persists, the module may be in failure.
Please consult your local Mitsubishi representative.
Power off the module power supply, set the IP address
setting switch in the range of 0 to 254, and then power on the
module power supply again.
Return the IP address setting switch to the previous setting.
Return the function setting switch 1 to 3 to the previous
setting.
Return the function setting switch 4 to the previous setting.