7.2

Configuring counters

Overview
You can configure the energy counters of the AI Energy Meter 400VAC ST as follows:
● Activate / Deactivate
● Start / stop counters using gate
● Set and reset start value
Energy counter gate
You have the option of starting and stopping the energy counter using the gate. To this
purpose you have to:
● Select the "Enable gate control for the energy counter" parameter in the configuration of
the AI Energy Meter 400VAC ST.
● Set the DQ bit for the "counter gate" in the user data in Control byte 1 of the output data
(Bit 6 in Control byte 1).
The "Enable gate control for the energy counter" parameter and the DQ bit for the "counter
date" behave like the parallel connection of contacts.
Figure 7-1
Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0)
Manual, 10/2017, A5E36061895-AB
Gate enabled
Energy counters
7.2 Configuring counters