Circuit diagram example
4.4 TIA Portal configuration
4.4.8

Assigning fail-safe addresses to ET 200SP

After setting the F parameters of the F-CM AS-i Safety ST module, the PROFIsafe-/F
destination address still has to be assigned to the extended module (real hardware).
Fail-safe ET 200SP modules do not have DIP switches with which you can assign the unique
F destination address (= PROFIsafe address) to each module. Instead, assign the PROFIsafe
address directly from STEP 7. F destination addresses are assigned in the hardware
configuration for the F module. An assignment is necessary when a system is commissioned
for the first time, for example. The F destination address can only be assigned if the PROFINET
device name is also assigned.
Open the shortcut menu of the F-CM AS-i Safety ST (right click on the F-CM AS-i Safety
module) and select "Assign F destination address". In the dialog which then appears, identify
the F-CM AS-i Safety ST module, and then assign the PROFIsafe address.
Figure 4-18
Repeat the described procedure for assigning the fail-safe address for the F-DQ module.
44
Assigning the PROFIsafe address
Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram
Function Manual, 08/2020, A5E44991382002A/RS-AB/002