Configuration Using the Web Interface
Event Type: Link Failure
Link: Select the port ID you would like to monitor.
How to configure: Check the box of the Ethernet port or ports you
want to monitor. When the selected ports are unlinked, the system
shorts the Relay Output and light the DO LED.
Event Type: Ping Failure
IP Address: Enter the IP address of the target device you want to
ping.
Reset Time (Sec): Enter the amount of time after a ping has failed
that you would like the relay output to turn off.
Hold Time (Sec): Enter the amount of time after a ping has failed
and relay output has been turned off, that you would like the relay
output to be turned back on.
How to configure: After selecting the Ping Failure event type, the
system changes the Relay Output to short state, lights the alarm
LED, and continuously pings the target device. When the ping failure
for the Reset Time times out, the system changes the Relay Output to
open state and turns off the alarm LED for the amount of time entered in the Hold Time. After the Hold Time
times out, the ES7506 starts sending ping commands to the remote device.
Example: When the Reset Time is set to 10 sec while the Hold Time is set to 40 sec the following occurs. After
ping has failed after 10 seconds (Reset Time), the system turns the Relay Output and Alarm LED off. After 40
seconds (Hold Time), the system turns the Relay Output and the Alarm LED on again.
Event Type: Super Ring Failure
Select Ring Failure and when the Ring topology changes, the ES7506
shorts the Relay out and light the Alarm LED.
Once you have finished configuring the settings, click the Apply
button to apply your configuration.
82 - Fault Relay
RocketLinx ES7506 User Guide: 2000529 Rev. F