D0: Total Power Consumption Every Five-Minute Period (0.001-Kwh Increments) - Omron KM50 Communications Manual

Smart power monitor
Table of Contents

Advertisement

● D0: Total Power Consumption Every Five-minute Period (0.001-kWh increments)
KM50-E Only
The total power consumption for every five-minute period can be read.
The total power consumption for every five-minute period can be read for only two days, the
present day and the previous day.
Specify the address for the time period to read in the service request PDU.
Example for Address 0001: The total power consumption from 00:05 to 00:10 will be read.
(The total power consumption for the specified five-minute period will be read.)
The total power consumption for every five-minute period for the present day cannot be read for
times that are in the future compared to the present time in the KM50 internal clock. If the total
power consumption is read for future times, the service response PDU will be returned with a
measurement value of 0.
If the read value exceeds 9,999 kWh, the precision of the lowest digit will be lost, so FFFF FFFF
will be returned as the measurement value in the service response PDU. If that occurs, read the
measurement value for 0.1-kWh increments.
The addresses are listed in the following table.
(Addresses are incremented by one for each five-minute period, so some addresses have been
omitted.)
Variable
Address
type
Total Power Consumption for
D0
0800
00:00 to 00:05 Today (kWh)
Total Power Consumption for
D0
0801
00:05 to 00:10 Today (kWh)
Total Power Consumption for
D0
0802
00:10 to 00:15 Today (kWh)
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
Total Power Consumption for
D0
091E
23:50 to 23:55 Today (kWh)
Total Power Consumption for
D0
091F
23:55 to 24:00 Today (kWh)
Total Power Consumption for
D0
0920
00:00 to 00:05 Yesterday
(kWh)
Total Power Consumption for
D0
0921
00:05 to 00:10 Yesterday
(kWh)
Total Power Consumption for
D0
0922
00:10 to 00:15 Yesterday
(kWh)
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
Total Power Consumption for
D0
0A3E
23:50 to 23:55 Yesterday
(kWh)
Total Power Consumption for
D0
0A3F
23:55 to 24:00 Yesterday
(kWh)
Parameter name
0000 0000 to 0098 967F hex (0.000 to 9,999.999)
*Three digits to the right of the decimal point (fixed).
Same as above.
Same as above.
⋅ ⋅ ⋅
(Omitted)
⋅ ⋅ ⋅
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
⋅ ⋅ ⋅
(Omitted)
⋅ ⋅ ⋅
Same as above.
Same as above.
3. 1 Variable Area
Set value (monitor value)
3-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents