Variable Area; Communications Data; C0 (Previous): Instantaneous Value Level - Omron KM50 Communications Manual

Smart power monitor
Table of Contents

Advertisement

3. 1 Variable Area

● Communications Data
Set values and monitor values are given in hexadecimal. Negative values are given as two's
complements. Values are converted to hexadecimal without the decimal point.
● Variable Area
• The KM50 variable area contains parameters that are in the same structure as those of the
KM100 and KM20-B40 (labeled below as "previous"), as well as parameters that are in the
data structure of the KM50-C (labeled below as "new"). Variable types C0 to C3 are the
previous types and C8 to CB are the new types. Other variable types are the same.
• The hexadecimal values that are given in the set value/monitor value column, are the
setting/monitoring ranges of the CompoWay/F. The actual ranges are given in parentheses.
Refer to the relevant parameters for textual descriptions.
● C0 (Previous): Instantaneous Value Level
Variable
Address
type
C0
0000
Instantaneous Voltage 1 (V)
Instantaneous Voltage 2 (V) Same as above.
C0
0001
C0
0002
Instantaneous Current 1 (A)
C0
0003
Instantaneous Current 2
C0
0004
Maximum Active Power (W)
Instantaneous Reactive
C0
0005
Power (kvar)
C0
0006
Instantaneous Power Factor
Instantaneous Frequency
C0
0007
(Hz)
Total Power Consumption
C0
0008
(kWh)
C0
000A
Status
C0
000B
Version
C0
000C
Instantaneous Voltage 3
C0
000D
Instantaneous Current 3
Instantaneous Active Power
C0
000E
(W)
Instantaneous Reactive
C0
000F
Power (var)
Calculated CO
C0
0010
consumption) (kgCO
Total Pulse Input Count for
*6
C0
0011
the Day (pulses)
Specific Power Consumption
C0
0012
(kWh/pulse)
C0
0013
Pulse Input ON Time
HIGH Total Power
*3
C0
0014
Consumption (kWh)
HIGH Total Power
*3
C0
0015
Consumption Ratio
*3
C0
0016
HIGH Total Time
Parameter name
0000 0000 to 000F 423F hex (0.0 to 99,999.9)
*One digit to the right of the decimal point (fixed).
0000 0000 to 0098 967F hex (0.00 to 99,999.99)
*Two digits to the right of the decimal point (fixed).
*1
(A) Same as above.
C465 3601 to 3B9A C9FF hex (−9,999,999.99 to 9,999,999.99)
*Two digits to the right of the decimal point (fixed).
Same as above.
FFFF FF9C to 0000 0064 hex (−1.00 to 1.00)
*Two digits to the right of the decimal point (fixed).
0000 01C2 to 0000 028A hex (45.0 to 65.0)
*One digit to the right of the decimal point (fixed).
0000 0000 to 05F5 E0FF hex (0.0 to 9,999,999.9)
*One digit to the right of the decimal point (fixed).
Refer to 3.2 3. 2
Example: 0000 0100 hex = version 1.00
0000 0000 to 0001 869F hex (0.0 to 9,999.9)
*2
(V)
*One digit to the right of the decimal point (fixed).
0000 0000 to 0098 967F hex (0.00 to 99,999.99)
*1
(A)
*Two digits to the right of the decimal point (fixed).
C465 3601 to 3B9A C9FF hex (−99,999,999.9 to 99,999,999.9)
*One digit to the right of the decimal point (fixed).
Same as above.
(total power
0000 0000 to 3B9A C9FF hex (0.0 to 99,999,999.9)
2
)
*One digit to the right of the decimal point (fixed).
2
0000 0000 to 0001 869F hex (0 to 99,999)
0000 0000 to 05F5 E0FF hex (0.000 to 99,999.999)
*Three digits to the right of the decimal point (fixed).
0000 0000 to 0000 HHMM hex
HH (hour): 0 to 18 hex (0 to 24)
MM (minutes): 0 to 3B hex (0 to 59)
0000 0000 to 05F5 E0FF hex (0.000 to 99,999.999)
*Three digits to the right of the decimal point (fixed).
0000 0000 to 0000 03E8 hex (0.000 to 1.000)
*4
*Three digits to the right of the decimal point (fixed).
0000 0000 to 0000 HHMM hex
HH (hour): 0 to 18 hex (0 to 24)
MM (minutes): 0 to 3B hex (0 to 59)

3. 1 Variable Area

Set value (monitor value)
Status Information
.
3-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents