Omron KM50 Communications Manual page 91

Smart power monitor
Table of Contents

Advertisement

Section 3 CompoWay/F Communications Data
Parameter type Address
C000
007F
C000
0080
C000
0081
C000
0082
C000
0083
C000
0084
C000
0085
C000
0086
C000
0087
C000
0088
C000
0089
C000
008A
*1: The fixed voltage for simple measurement can be set in increments of 0.1 V. This voltage
could be set in increments of 1 V for the KM100.
*2: The data length will be 8 bits if Modbus is set as the communications protocol.
*3: If Modbus is set as the communications protocol, the number of stop bits will be set
automatically according to the vertical parity.
No vertical parity: 2 bits
Odd or even vertical parity: 1 bit
*4: The conversion coefficient varies with the region. Please check the home page of your power
company. The default setting is the CO
2009.
*5: These addresses are used only for the KM50-E. They cannot be read or written with the
KM50-C.
3-50
Default
Parameter name
setting
Incorrect
Incorrect Wiring
wiring
Detection
detected.
Conversion to
Monetary Cost Rate
10.000
Setting
_JPY
(204A
Currency Setting
5059
hex)
Pulse
Input
Pulse Conversion 1
Count 1
Target
for the
Day
Pulse
Input
Pulse Conversion 2
Count 2
Target
for the
Day
Coefficient Setting 1 1
Coefficient Setting 2 1
Decimal Point
0000
Position Setting 1
Decimal Point
0000
Position Setting 2
M3-1
Display Unit Setting 1
(4D33 2
F31 hex)
M3-2
Display Unit Setting 2
(4D33 2
F32 hex)
VT Secondary
110 V
Voltage
coefficient for Kyushu Electric Power Company for
2
Set value (monitor value)
0000 0000 hex: No incorrect wiring detected.
0000 0001 hex: Incorrect wiring detected.
0000 000 to 0001 869F hex (0 to 99.999)
Three digits to the right of the decimal point (fixed).
Input 1-byte one character in ASCII.
0 to 9: 30 to 39 hex
A to Z: 41 to 5A hex
/, -, space: 2F, 2D, 20 hex
0000 0000 hex: Total Pulse Input Count for the Day
0000 0001 hex: Pulse Input Count 1 for the Day
0000 0002 hex: Pulse Input Count 2 for the Day
0000 0003 hex: Sum Total Pulse Input Count
0000 0004 hex: Total Pulse Input Count 1
0000 0005 hex: Total Pulse Input Count 2
0000 0000 hex: Total Pulse Input Count for the Day
0000 0001 hex: Pulse Input Count 1 for the Day
0000 0002 hex: Pulse Input Count 2 for the Day
0000 0003 hex: Sum Total Pulse Input Count
0000 0004 hex: Total Pulse Input Count 1
0000 0005 hex: Total Pulse Input Count 2
0000 0000 to 0000 270F hex (0 to 9,999)
0000 0000 to 0000 270F hex (0 to 9,999)
0000 0000 hex: 0000 (No decimal points)
0000 0001 hex: 000.0 (One place below the
decimal point)
0000 0002 hex: 00.00 (Two places below the
decimal point)
0000 0003 hex: 0.000 (Three places below the
decimal point)
0000 0000 hex: 0000 (No decimal points)
0000 0001 hex: 000.0 (One place below the
decimal point)
0000 0002 hex: 00.00 (Two places below the
decimal point)
0000 0003 hex: 0.000 (Three places below the
decimal point)
Input 1-byte one character in ASCII.
0 to 9: 30 to 39 hex
A to Z: 41 to 5A hex
/: 2F hex, -: 2D hex, space: 20 hex
Input 1-byte one character in ASCII.
0 to 9: 30 to 39 hex
A to Z: 41 to 5A hex
/: 2F hex, -: 2D hex, space: 20 hex
0000 0000 hex: 110 V
0000 0001 hex: 220 V