● Changing Set Values
Set the parameters while the Power Monitor is in a Setting Mode
However, even if the set values are changed, the changes will not be applied in the Setting Mode.
Changes to parameters that are made in a Setting Mode are enabled by changing to
Measurement Mode.
● Communications Example for Write Parameter Area
Here, the Special CT type is set to 50A.
(It is assumed that the Power Monitor is already in a Setting Mode.)
Service Request PDU
0 2 0 2 C 0 0 0 0 0 1 9 8 0 0 1 0 0 0 0 0 0 0 1
Parameter
MRC
SRC
type
Service Response PDU
0 2 0 2 0 0 0 0
Response
MRC
SRC
code
The following are given for set value/monitor value of the Special CT type in 5.3 Parameter Area.
0000 0000 hex:
KM20-CTF-5A (5A)
0000 0001 hex:
KM20-CTF-50A (50A)
0000 0002 hex:
KM20-CTF-100A (100A)
0000 0003 hex:
KM20-CTF-200A (200A)
0000 0004 hex:
KM20-CTF-400A (400A)
0000 0005 hex:
KM20-CTF-600A (600 A)
Therefore, 0000 0001 hex means 50A.
No. of
Write start
elements
address
2. 3 Detailed Descriptions of Services
Write data
2-13