● D6: Pulse Input ON Time for Every Day
The pulse ON time for every day can be read.
The pulse input ON time for every day can be read for the present day and the last eight days.
Specify the address for the day to read in the service request PDU.
Variable
Address
type
Present Pulse Input ON Time
D6
0000
for Today
Pulse Input ON Time One Day
D6
0001
Ago
Pulse Input ON Time Two
D6
0002
Days Ago
Pulse Input ON Time Three
D6
0003
Days Ago
Pulse Input ON Time Four
D6
0004
Days Ago
Pulse Input ON Time Five
D6
0005
Days Ago
Pulse Input ON Time Six Days
D6
0006
Ago
Pulse Input ON Time Seven
D6
0007
Days Ago
Pulse Input ON Time Eight
D6
0008
Days Ago
● D7: Specific Power Consumption for Every Day
The specific power consumption for every day can be read.
The specific power consumption for every day can be read for the present day and the last eight
days.
Specify the address for the day to read in the service request PDU.
If the read value exceeds 99,999.999 kWh/pulse, the precision of the lowest digit will be lost, so
FFFF FFFF will be returned as the measurement value in the service response PDU.
Variable
Address
type
Present Specific Power
Consumption for Today
D7
0000
(kWh/pulse)
Specific Power Consumption
D7
0001
for One Day Ago (kWh/pulse)
Specific Power Consumption
D7
0002
for Two Days Ago (kWh/pulse)
Specific Power Consumption
D7
0003
for Three Days Ago
(kWh/pulse)
Specific Power Consumption
D7
0004
for Four Days Ago (kWh/pulse)
Specific Power Consumption
D7
0005
for Five Days Ago (kWh/pulse)
Specific Power Consumption
D7
0006
for Six Days Ago (kWh/pulse)
Specific Power Consumption
D7
0007
for Seven Days Ago
(kWh/pulse)
Specific Power Consumption
D7
0008
for Eight Days Ago
(kWh/pulse)
Parameter name
0000 HHMM hex
HH (hour): 0 to 18 hex (0 to 24)
MM (minutes): 0 to 3B hex (0 to 59)
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Parameter name
0000 0000 to 05F5 E0FF hex (0.000 to 99,999.999)
*Three digits to the right of the decimal point (fixed).
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
3. 1 Variable Area
Set value (monitor value)
Set value (monitor value)
3-23