Omron KM50 Communications Manual page 149

Smart power monitor
Table of Contents

Advertisement

Section 5 Modbus Communications Data
Address
Parameter name
F00F
Protection Setting
F010
Special CT Type
F011
CO
Coefficient
2
F012
Protocol Selection
F013
Average Count
F014
Event Input Setting
F015
Event Input 1
NPN/PNP Input Mode
Setting
F016
Event Input 2
NPN/PNP Input Mode
Setting
F017
Event Input 1
Input Mode Setting
F018
Event Input 2
Input Mode Setting
F019
Measurement Start
Time
F01A
Measurement End
Time
*4
F01B
Buzzer
*4
F01C
Three-state Target
*4
F01D
Three-state HIGH
*5
Threshold
*4
F01E
Three-state LOW
*5
Threshold
*4
F01F
Three-state Hysteresis 0.0%
*6
F020
Active Power Alarm
Setting
*7
F021
Active Power Alarm
Upper Limit Threshold
F022
Active Power Alarm
Hysteresis
F023
Active Power Alarm
OFF Delay
F024
Total Power
Consumption Selection
5-42
Default setting
0
0000 0000 hex: Protection level 0
0000 0001 hex: Protection level 1
0000 0002 hex: Protection level 2
2
0000 0000 hex: KM20-CTF-5A (5 A)
0000 0001 hex: KM20-CTF-50A (50 A)
0000 0002 hex: KM20-CTF-100A (100 A)
0000 0003 hex: KM20-CTF-200A (200 A)
0000 0004 hex: KM20-CTF-400A (400 A)
0000 0005 hex: KM20-CTF-600A (600 A)
0.387
0000 0000 to 0001 869F hex
(0.000 to 99.999 kg-CO
*Three digits to the right of the decimal point (fixed).
CompoWay/F
0000 0000 hex: CompoWay/F
0000 0001 hex: Modbus
OFF
0000 0000 hex: OFF
0000 0001 hex: 2 times
0000 0002 hex: 4 times
0000 0003 hex: 8 times
0000 0004 hex: 16 times
0000 0005 hex: 32 times
0000 0006 hex: 64 times
0000 0007 hex: 128 times
0000 0008 hex: 256 times
0000 0009 hex: 512 times
0000 000A hex: 1,024 times
*8
P.CSP
0000 0000 hex: P.CSP (pulse input count)
0000 0001 hex: H-ON (pulse input ON time measurement)
0000 0002 hex: 3-ST (Three-state Classification) (KM50-E
PNP
0000 0000 hex: PNP
0000 0001 hex: NPN
PNP
0000 0000 hex: PNP
0000 0001 hex: NPN
N-O
0000 0000 hex: N-O (normally open)
0000 0001 hex: N-C (normally closed)
N-O
0000 0000 hex: N-O (normally open)
0000 0001 hex: N-C (normally closed)
00:00
0000 0000 to 0000 HHMM hex (00:00 to 23:59)
HH (hour):
MM (minutes): 00 to 3B hex (00 to 59)
24:00
0000 HHMM to 0000 HHMM hex (00:01 to 24:00)
HH (hour):
MM (minutes): 00 to 3B hex (00 to 59)
ON
0000 0000 hex: OFF
0000 0001 hex: ON
*8
NONE
0000 0000 hex: Power
0000 0001 hex: Current
0000 0002 hex: Voltage
0000 0003 hex: NONE
50.0%
0000 0001 to 0000 05DC hex (0.1% to 150.0%)
*One digit to the right of the decimal point (fixed).
10.0%
0000 0000 to 0000 05DB hex (0.0% to 149.9%)
*One digit to the right of the decimal point (fixed).
0000 0000 to 0000 00C7 hex (0.0% to 19.9%)
*One digit to the right of the decimal point (fixed).
ON
0000 0000 hex: OFF
0000 0001 hex: ON
80.0%
0000 0000 to 0000 05DC hex (0.0% to 150.0%)
*One digit to the right of the decimal point (fixed).
5.0%
0000 0000 to 0000 00C7 hex (0.0% to 19.9%)
*One digit to the right of the decimal point (fixed).
3.0 s
0000 0000 to 0000 03E7 hex (0.0 to 99.9 s)
*One digit to the right of the decimal point (fixed).
Regeneration
0000 0000 hex: Regenerated Energy
0000 0001 hex: Total Leading Reactive Power
0000 0002 hex: Total Lagging Reactive Power
0000 0003 hex: Total Reactive Power Consumption
Set value (monitor value)
/kWh)
2
only)
00 to 17 hex (0 to 23)
00 to 18 hex (0 to 24)
Consumption
Consumption