C1 (Previous): Average Value Level - Omron KM50 Communications Manual

Smart power monitor
Table of Contents

Advertisement

Section 3 CompoWay/F Communications Data
*2 The order of voltages 1, 2, and 3 that are read with the previous addresses are as follows:
Wiring method
Single-phase,
2-wire
Single-phase,
3-wire
Three-phase,
3-wire
Three-phase,
4-wire
---: These values will read as 0.
*3 These addresses can be read only with the KM50-E. They cannot be read with the KM50-C.
*4 The ratios for various values read as 1.000 for 100% for the status from the start time until the
end time.
*5 Temperatures are read out in the unit that has been set. Conversion between Celsius and
Fahrenheit is made using the following formulas. If both values are required, convert the
temperature in the host device.
*6 The pulse input counts are counter values that are reset on a daily basis. The total pulse input
count is not reset on a daily basis, rather it is reset to zero when the count upper limit is
reached, and starts counting again. Counter 1 and counter 2 are individual count values that
can be read separately. The total counter reads the sum of counter 1 and counter 2. A
summary is shown in the following table.
Parameter
Pulse Input Count 1 for the Day
Pulse Input Count 2 for the Day
Total Pulse Input Count for the Day
Total Pulse Input Count 1
Total Pulse Input Count 2
Sum Total Pulse Input Count
*7 Values after Recovering from a Power Interruption
The following measurement values are saved to the memory for every 5-minute period.
Therefore, when the power supply is turned ON, the last value that was saved for a
five-minute period while the Power Monitor was ON will be read out, rather than the value right
before the power was interrupted. The measurement will continue.
Total power consumptions, pulse input ON time, pulse input count, specific power
consumption, and three-state total power consumptions
*8 Digits That Are Read Out
The upper digits and lower digits of a converted value can be read out separated. However,
there are only seven significant digits when the upper and lower digits are combined.
● C1 (Previous): Average Value Level
This variable type is not used by the KM50-C/-E.
(The KM50-C/-E do not support averaging for the data logging cycle.)
3-6
Previous/new addresses
Voltage 1
Voltage 2
Voltage 3
---
---
Vrs
Vrn
Vsn
Vrs
Vrs
Vst
Vtr
Vrn
Vsn
Vtn
Input count for input 1
Input count for input 2
Sum of input counts for inputs 1 and
2
Input count for input 1
Input count for input 2
Sum of input counts for inputs 1 and
2
Read out value
Reset on a daily basis.
Reset when upper limit
is reached.
Reset condition