Omron KM50 Communications Manual page 80

Smart power monitor
Table of Contents

Advertisement

● E1: Minimum Measurement Values
The minimum measurement values can be read.
The minimum measurement values for every day can be read for the present day and the last eight
days. However, the reactive power can be read only for the present day.
Specify the address for the day and measurement item to read in the service request PDU.
The minimum value and the time when the value was recorded can be read.
You can read both the measurement time and measurement value, only the measurement time, or
only the measurement value.
Addresses are defined as follows:
0
0: The first digit of the address is always 0.
: Indicates the day. 0: Present day, 1: One day ago, 2: Two days ago, .., 8: Eight days ago
: Indicates the measurement time or the measurement item.
Variable
Address
type
E1
0000
Voltage 1
Today
E1
0001
E1
0002
Voltage 2
Today
E1
0003
E1
0004
Voltage 3
Today
E1
0005
E1
0006
Current 1
Today
E1
0007
E1
0008
Current 2
Today
E1
0009
E1
000A
Current 3
Today
E1
000B
E1
000C
Power Factor
Today
E1
000D
E1
000E
Active Power
Today
E1
000F
E1
0010
Active Power
Today
E1
0011
E1
0012
Reactive
Power Today
E1
0013
Parameter name
0000 HHMM hex
Measurement
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Time
0000 0000 to 000F 423F hex (0.0 to 99,999.9)
Measurement
*One digit to the right of the decimal point (fixed).
Value (V)
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
0000 0000 to 000F 423F hex (0.0 to 999,999.9)
Value (V)
*One digit to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
0000 0000 to 000F 423F hex (0.0 to 99,999.9)
Value (V)
*One digit to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
0000 0000 to 0098 967F hex (0.000 to 99,999.999)
Value (A)
*Three digits to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
0000 0000 to 0098 967F hex (0.000 to 99,999.999)
Value (A)
*Three digits to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
0000 0000 to 0098 967F hex (0.000 to 99,999.999)
Value (A)
*Three digits to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
FFFF FF9C to 0000 0064 hex (
Value
*Two digits to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
C465 3601 to 3B9A C9FF hex (
Value (W)
*One digit to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
C465 3601 to 3B9A C9FF hex (
Measurement
*Two digits to the right of the decimal point (fixed).
Value (kW)
*Two digits to the right of the decimal point (fixed).
Measurement
0000 HHMM hex
Time
HH (hour): 0 to 17 hex (0 to 23), MM (minutes): 0 to 3B hex (0 to 59)
Measurement
C465 3601 to 3B9A C9FF hex (
Value (var)
*One digit to the right of the decimal point (fixed).
3. 1 Variable Area
Set value (monitor value)
1.00 to 1.00)
99,999,999.9 to 99,999,999.9)
9,999,999.99 to 9,999,999.99)
99,999,999.9 to 99,999,999.9)
3-39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents