Section 5 Functions and Operations
5.20 Changing the Display Refresh Period
2
d. ref
L
(D.REF)
0
L
0."
Displays "
L
sv. dsp
2
L
off
2."
Displays "
L
d. ref
2
L
off
d. ref
2
L
off
d. ref
2
L
2
color
2
L
grn-r
123. 4
123. 4
5-60
When measurement values change rapidly, the accompanying
changes in the display value can cause flickering, decreasing
readability. Readability of the display can be improved in such
situations by lengthening the display refresh period to suppress
flickering.
The display refresh period is set using the following parameter.
Parameter
Display refresh period
d.ref
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
L
the initial setting level.
3 s min.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the L [LEVEL] Key several times to move to the display
L
adjustment level.
2" is displayed on the level/bank display to indicate the
• "
L
adjustment level.
C Press the M [MODE] Key to switch to the PV display to "d.ref".
M
D Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
E Use the U [UP] Key to change the set value.
U
F Press the M [MODE] Key to switch to the next parameter.
M
• The set value is registered.
G Press the L [LEVEL] Key for at least 1 s to return to RUN level.
L
1 s min.
"5.9 Averaging Input" → P.5-36
Remarks
Display adjustment level
Set value
Meaning of set value
off
Every 50 ms
0. 5
Every 0.5 s
1
Every 1 s
2
Every 2 s
4
Every 4 s
R
P C