D1: Total Power Consumption Every Five Minutes (0.001-Kwh Increments) - Omron KM50 Communications Manual

Smart power monitor
Table of Contents

Advertisement

● D1: Total Power Consumption Every Five Minutes (0.001-kWh increments)
The total power consumption every five minutes can be read.
The total power consumption every five minutes can be read for only two days, the present day
and the previous day.
Specify the address for the time period to read in the service request PDU.
Example for Address 0001: The total power consumption at 00:10 will be read.
(The total power consumption for the specified time will be read.)
The total power consumption every five minutes for the present day cannot be read for times that
are in the future compared to the present time in the KM50 internal clock. If the total power
consumption is read for future times, the service response PDU will be returned with a
measurement value of 0.
If the read value exceeds 9,999 kWh, the precision of the lowest digit will be decreased, so FFFF
FFFF will be returned as the measurement value in the service response PDU. If that occurs, read
the measurement value for 0.1-kWh increments.
The addresses are listed in the following table.
(Addresses are incremented by one for each five minutes, so some addresses have been omitted.)
Variable
Address
type
Total Power Consumption for
D1
0800
00:05 Today (kWh)
Total Power Consumption for
D1
0801
00:10 Today (kWh)
Total Power Consumption for
D1
0802
00:15 Today (kWh)
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
Total Power Consumption for
D1
091E
23:55 Today (kWh)
Total Power Consumption for
D1
091F
24:00 Today (kWh)
Total Power Consumption for
D1
0920
00:05 Yesterday (kWh)
Total Power Consumption for
D1
0921
00:10 Yesterday (kWh)
Total Power Consumption for
D1
0922
00:15 Yesterday (kWh)
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
⋅ ⋅ ⋅
Total Power Consumption for
D1
0A3E
23:55 Yesterday (kWh)
Total Power Consumption for
D1
0A3F
24:00 Yesterday (kWh)
Parameter name
0000 0000 to 0098 967F hex (0.000 to 9,999.999)
*Three digits to the right of the decimal point (fixed).
Same as above.
Same as above.
⋅ ⋅ ⋅
(Omitted)
⋅ ⋅ ⋅
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
⋅ ⋅ ⋅
(Omitted)
⋅ ⋅ ⋅
Same as above.
Same as above.
3. 1 Variable Area
Set value (monitor value)
3-15