Addresses 6800 To 6808 Hex: Low Total Power Consumption Every Day (0.001-Kwh Increments); Addresses 6900 To 6908 Hex: Low Total Power Consumption Ratio Every Day - Omron KM50 Communications Manual

Smart power monitor
Table of Contents

Advertisement

Section 5 Modbus Communications Data
● Addresses 6800 to 6808 hex: LOW Total Power Consumption Every Day
(0.001-kWh increments) KM50-E Only
The LOW total power consumption for every day can be read.
The LOW total power consumption for every day can be read for the present day and the last eight
days.
Specify the address for the day to read in the service request PDU.
If the read value exceeds 99,999.999 kWh, the precision of the lowest digit will be lost, so FFFF
FFFF will be returned as the measurement value in the service response PDU.
Address
Present LOW Total Power
6800
Consumption for Today (kWh)
LOW Total Power Consumption for
6801
00:00 to 24:00 One Day Ago (kWh)
LOW Total Power Consumption for
6802
00:00 to 24:00 Two Days Ago (kWh)
LOW Total Power Consumption for
6803
00:00 to 24:00 Three Days Ago (kWh)
LOW Total Power Consumption for
6804
00:00 to 24:00 Four Days Ago (kWh)
LOW Total Power Consumption for
6805
00:00 to 24:00 Five Days Ago (kWh)
LOW Total Power Consumption for
6806
00:00 to 24:00 Six Days Ago (kWh)
LOW Total Power Consumption for
6807
00:00 to 24:00 Seven Days Ago (kWh)
LOW Total Power Consumption for
6808
00:00 to 24:00 Eight Days Ago (kWh)
● Addresses 6900 to 6908 hex: LOW Total Power Consumption Ratio Every Day
KM50-E Only
The LOW total power consumption ratio for every day can be read.
The LOW total power consumption ratio for every day can be read for the present day and the last
eight days.
Specify the address for the day to read in the service request PDU.
Address
Present LOW Total Power
6900
Consumption Ratio for Today (%)
LOW Total Power Consumption Ratio
6901
for 00:00 to 24:00 One Day Ago (%)
LOW Total Power Consumption Ratio
6902
for 00:00 to 24:00 Two Days Ago (%)
LOW Total Power Consumption Ratio
6903
for 00:00 to 24:00 Three Days Ago (%)
LOW Total Power Consumption Ratio
6904
for 00:00 to 24:00 Four Days Ago (%)
LOW Total Power Consumption Ratio
6905
for 00:00 to 24:00 Five Days Ago (%)
LOW Total Power Consumption Ratio
6906
for 00:00 to 24:00 Six Days Ago (%)
LOW Total Power Consumption Ratio
6907
for 00:00 to 24:00 Seven Days Ago (%)
LOW Total Power Consumption Ratio
6908
for 00:00 to 24:00 Eight Days Ago (%)
5-32
Parameter name
0000 0000 to 05F5 E0FF hex (0.000 to 99,999.999)
*Three digits to the right of the decimal point (fixed).
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Parameter name
0000 0000 to 0000 03E8 hex (0.000 to 1.000)
*Three digits to the right of the decimal point (fixed).
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.
Same as above.