Functions
2.1 General
reclosure does not have a general pickup signal for starting the action times, select ... Trip without T-
action.
For the trip circuit supervision set at address 140 Trip Cir. Sup. the number of trip circuits to be monitored:
1 trip circuit, 2 trip circuits or 3 trip circuits, unless you omit it (Disabled).

2.1.1.3 Settings

Addr.
Parameter
103
Grp Chge OPTION
106
VT CONNECTION
107
CT CONNECTION
110
Trip mode
126
Back-Up O/C
133
Auto Reclose
134
AR control mode
135
Synchro-Check
137
U/O VOLTAGE
139
BREAKER FAILURE
140
Trip Cir. Sup.
26
Setting Options
Disabled
Enabled
3phase
1phase
NO
YES
NO
3pole only
1-/3pole
Disabled
TOC IEC
TOC ANSI
TOC IEC /w 3ST
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
enabled w/ 3I0>
Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Default Setting
Disabled
Setting Group Change Option
3phase
Voltage transformer connection
YES
Current transformer connection
3pole only
Trip mode
Disabled
Backup overcurrent
Disabled
Auto-Reclose Function
Trip w/ Tact
Auto-Reclose control mode
Disabled
Synchronism and Voltage Check
Disabled
Under / Overvoltage Protection
Disabled
Breaker Failure Protection
Disabled
Trip Circuit Supervision
C53000-G1176-C159-3, Release date 05.2009
Comments
SIPROTEC, 7VK61, Manual