39
E3G091 Remote transmission interface
39.1
Overview
39.2
Application
39.3
Key data
39.4
Important components
Building Technologies
Fire Safety & Security Products
Interface for remote transmission equipment with several alarm criteria
Designed for 4 channels
Enables activation via make or break contact as well as the de-coupled activa-
tion of all channels upon "Emergency alarm"
Test LED for each channel (active upon activation)
Activation upon "Emergency alarm"
Card format 100 mm x 100 mm
Only necessary in systems with several remote alarm criteria
Voltage
Output contacts
Contact load
Quiescent current
max. current
Terminal block X15 (20 terminals)
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
–
for direct connection of the periphery
Card chassis
mounted on module chassis
–
1
X
H3
H1
H2
TEST
K1
2
K2
S1
K3
K4
3
E3G091 Remote transmission interface
20...32 VDC
4
30 VA
at 24V
0 mA
DC
100 mA
Y1
Y
Y6
6
5
4
11
001260_k_en_--.doc
02.2005
163