B3R051 Parallel Indicator Terminal (Supersedes B3R050) - Siemens Cerberus CS1140 Manual

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

47
B3R051 Parallel indicator terminal
47.1
Overview
47.2
Application
47.3
Key data
Building Technologies
Fire Safety & Security Products
B3R051
Templates for inscription strips see document 006516
Option to control terminal AlgoPilot B3Q... or to LON/Mimic Display converter
K3I050
Allows additional display fields
Unit with 2 x 12 display fields each with a red and yellow LED
Individual allocation of individual display fields
Max. 24 units, however max. 8 addresses
Communication is via a special serial bus
Line and device not monitored
"Lamp test" is contained in the menu function of AlgoPilot B3Q...
Installation
The parallel indicator terminal B3R051 fits in the following housings:
plastic housing "small" H23G220 (1x B3R051)
housing H28G200 with door H28T120 for 4x B3R051
with door H28T130 for 1x B3R051 (and plan compartment)
Positioning
Immediately next to or in the immediate vicinity of the control terminals AlgoPilot
B3Q... or up to 1000m away in a separate housing
Operating voltage
Current consumption
at 24 V
at 9 V
at 45 V

B3R051 Parallel indicator terminal (supersedes B3R050)

(supersedes B3R050)
AlgoPilot B3Q...
9..45 VDC
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA
197
001260_k_en_--.doc
02.2005