Siemens Cerberus CS1140 Manual page 146

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

E3G060 Control module "monitored" (Part No 542539)
35.5
Connections
E3G060
common for inputs 15... 20
Monitored
LED
control line 1
Monitored
LED
control line 2
Monitored
LED
control line 3
Monitored
LED
control line 4
LED
Monitored
Module chassis ground
control line 5
Monitored
LED
control line 6
Control input 1
Control input 2
Control input 3
Control input 4
Control input 5
Control input 6
Plug-in terminals
Supply for
I-Bus modules
Plug-in terminals
Horn Synchronization output or
Horn oscillator input
External horn supply
Double flat cable header
Data communication
I-Bus modules
146
Building Technologies
Fire Safety & Security Products
(Part No 542539)
X1
Terminal block
1
-
2
H1
24V
F1
+
3
1)
-
4
H2
F3
+
5
-
6
H3
+
7
F5
-
8
H4
F7
+
9
-
10
H5
11
(connect to chassis ground)
+
12
F9
-
13
24V
H6
F11
+
14
15
16
17
18
19
20
K1
-
1
blue
GND
-
2
blue
+
3
5V
green
F19
24V
+
4
red
K2
1
2
K3
Plug-in terminals
1
-
0V
-
2
+
3
24V / 12A
+
4
ST1
1) The indicated polarity at the terminals 2...14 applies to the active state
max. 2A
4.75kΩ
max. 2A
4.75kΩ
control inputs:
to invert global defined horn mode
(switch S7) individually for each horn
output from (constant / intermitted)
from previous I-Bus modules
to other I-Bus modules
GND
time relay (external horn oscillator)
E3X10.
(Relay / contact must not be outside
the control unit housing)
to other E3G060 (for horn synchronization)
(all E3G060 in the same housing)
24V / 12A (only external supply)
from previous I-Bus modules
to other I-Bus modules
001260_k_en_--.doc
02.2005