Emergency operation

4
Emergency operation
CT
Emergency operation circuit external
(3 additional wires)
C-Bus
CC/CI
20
Building Technologies
Fire Safety & Security Products
An alarm which occurs during system failure is displayed at the control panel as a
"Collective alarm" (without location). This is achieved by the emergency operating
circuit permanently integrated in the system.
Reduced alarm messages in emergency operation mode
Collective alarm at AlgoPilot B3Q... level (visual and buzzer)
Alarm horns are activated and can be silenced at AlgoPilot B3Q... control con-
sole level
Remote alarm is activated via contact at the CPU
Response indicator at detector flashes (except with collective detectors)
Emergency operation circuit at C-Bus level (external)
Comprises the functions "Collective alarm" and "Silence alarm horns"
Requires 3 additional wires between E3X10. and AlgoPilot B3Q...
The line 'Emergency operation circuit fire alarm' is electrically monitored
Function 'Monitoring' must, if not used, be set to inactive (AlgoWorks)
Emergency operation circuit between the individual stations is designed for spe-
cific systems
Emergency operation circuit at I-Bus level (internal)
Comprises the functions "Emergency alarm" and "Silence alarm horns" at the va-
rious I-Bus modules
Integrated in the I-Bus flat cable (for this purpose 2 lines lead via all modules to
the E3X10.)
CC/CI
CK
Emergency operation circuit internal
CC/CI
E3M...
I-Bus
E3G080
B3Q440
001260_k_en_--.doc
02.2005