Commissioning I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored) FCI2009-A1

16 Commissioning I/O card (remote
58
Building Technologies
Fire Safety
transmission) FCI2007-A1 and I/O card
(horn/monitored) FCI2009-A1
With the I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored)
FCI2009-A1, the monitored outputs are monitored for short-circuit and open line.
The resistance values of the lines may be read in and stored at the push of a
button. If a deviation from the quiescent value is detected, the control panel
evaluates a short-circuit or an open line.
The following outputs must be calibrated upon commissioning:
FCI2007-A1: 'OUT1' to 'OUT3'
FCI2009-A1: 'OUT1' to 'OUT8'
You will find more information about the FCI2007-A1 and FCI2009-A1 I/O cards
and planning monitored outputs in documents A6V10210362 and A6V10210368.
See chapter 'Applicable documents'.
S501
I/O card FCI2007-A1 and/or FCI2009-A1
S501
Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the S501 button.
The resistance values are read in.
You can also read in the resistance values via the control panel's Person Machine
Interface.
A6V10210416_f_en_--
14.01.2013