E3M070 Line module "Interactive" (superseded by E3M071)
19
E3M070 Line module "Interactive"
19.1
Overview
19.2
Key data
82
Building Technologies
Fire Safety & Security Products
Line module for interactive detectors
I-Bus module with line processor and independent emergency operation proces-
sor
Designed for 1 loop line or stub line
With 24 V supply output
Line inputs and supply outputs protected against over voltage
Card format 100 mm x 200 mm
I-Bus address is set at programming switch "S3"
Addresses
Number of wires
Twisted cable
Line resistance
Line capacitance
Short-circuit proof line
T-branch
Quiescent current at 24 V
Current at supply output
1) Limitations –> see document 1102
2) with MICC max. 1000 m from the control unit to the last detector, with RADOX
max. 2000 m
Terminal block X20 (20 terminals)
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
–
for direct connection of the periphery
Card chassis
mounted on module chassis
–
(superseded by E3M071)
...100 1)
2
necessary
...100 Ω 1) 2)
...300 nF 1) 2)
yes
(line separator in each manual call point and E/A module, automatic
detectors are available with or without line separator)
yes
215 mA with 100 detectors and supply output unloaded
(135 mA without detector)
...500 mA / 20...30 VDC (not stabilized)
001260_k_en_--.doc
02.2005