7
E3X100 Master module
7.1
Overview
7.2
Application
Building Technologies
Fire Safety & Security Products
Main evaluating unit for the CS1140 series of fire detection control units with the
function of "Main CPU"
With small systems, the B3Q... control console can also take over the "Main
CPU" function.
Processes up to 16 I–Bus modules
Various interfaces, control inputs, control outputs and supply outputs
EPROM as program memory
RAM depending on application
Lithium battery for RAM buffering
Integrated battery–charger and monitoring function unit as I–Bus module
Integrated emergency operation electronics
Card format 366.8 mm x 200 mm
Processing capacity see –> document 'Planning' (1076 EP5, 008725 EP7F-Z1)
For larger systems with stations CC1142 or CC1143..
According to system size (table of quantities) choose the corresponding
EPROM+RAM set:
for CC1142
for CC1143
Recommended EPROMs: 27C040, 27C4001 (512Kx8Bit, 100 ns, DIP32)
X15
Terminal blocks X15 and X16 (20 terminals each). With EMI protect..
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Terminal block X17 (20 terminals) Only for internal connections.
X16
mounted on module chassis
for the connection of the prefabricated cable for battery, temperature sensor and
power unit
X17
Battery terminals (+, –, Centre tap)
Temperature sensor
Card chassis

E3X100 Master module (superseded by E3X101)

(superseded by E3X101)
–>
CCQ00xxx
Z3S070
–>
CCW00xxx
Z3S070
K3N010
(EPROM set 2x 512Kx8Bit)
(RAM set 2x 512Kx8Bit)
(EPROM set 2x 512Kx8Bit)
(RAM set 2x 512Kx8Bit)
(RAM board 1x 1MB)
001260_k_en_--.doc